1. Series Configuration (Left Side of Diagram)

Description

  • The motion sensor and time clock are connected in series.

  • Both must be activated (closed circuit) for the air conditioning system to turn ON.

  • If either one deactivates, the circuit opens and the unit turns OFF.

Application

This setup is used when you want both conditions to be met before operation is allowed — for example:

  • Office applications: System operates only during scheduled hours and when motion is detected.

  • Energy-saving logic: Prevents after-hours operation unless occupancy is confirmed.

Logic Summary

ConditionUnit State
Motion detected and Time Clock ONON
Motion not detected or Time Clock OFFOFF

Advantages

  • Saves energy by ensuring operation only when needed.

  • Ideal for strict energy-controlled environments.


2. Parallel Configuration (Right Side of Diagram)

Description

  • The motion sensor and time clock are connected in parallel.

  • If either device closes its contact, the circuit activates and the unit turns ON.

  • The system will remain ON as long as one of the two stays active.

Application

Used when either occupancy or schedule should enable the system:

  • Retail environments: Operate on schedule but also activate early if motion is detected.

  • Showrooms or corridors: Allow manual or automatic operation without full dependence on time scheduling.

Logic Summary

ConditionUnit State
Motion detected or Time Clock ONON
Motion not detected and Time Clock OFFOFF

Advantages

  • More flexible operation.

  • Useful for comfort-first environments with extended or unpredictable usage.


3. Integration into VRF / Split Systems

In systems like Fujitsu AIRSTAGE VR-II, this type of external control is connected to the External Input Terminal on the indoor PCB or control board.

  • “External Input” can be configured (via DIP switch or controller setting) to respond to contact closure from devices like:

    • Motion sensors

    • Time clocks

    • Building management system (BMS) relays

Example Setup

  • Terminal 1: Common (COM)

  • Terminal 2: External ON/OFF signal (Dry Contact)

  • Terminal 3: Ground or additional input (varies by model)

When the external contacts close according to the series or parallel wiring method, the indoor unit interprets it as a run command.


4. Best Practice Notes

  • Always use dry contact (volt-free) inputs to avoid electrical interference.

  • Series wiring = logic “AND” (both must be active).

  • Parallel wiring = logic “OR” (either one can activate).

  • Verify polarity or signal type per manufacturer’s control schematic.

  • For Fujitsu VRF systems, refer to the indoor PCB CN16/CN17 terminals for motion sensor or time clock inputs.