General Assist Technical Reference

Air Conditioning Component Test Sheets

Electrical, communication, inverter, sensor and actuator checks
Reference readings for qualified Fujitsu air conditioning service technicians
These test sheets consolidate typical readings used to assess communication circuits, inverter power components, fan motors, thermistors, electronic expansion valves and pressure transducers before parts are replaced.
Electrical safety: Testing may involve 240 V AC, 400–415 V AC and DC voltages up to approximately 600 V. Work must only be completed by appropriately licensed and competent personnel. Isolate and prove the supply is de-energised before disconnecting plugs or completing resistance and diode tests. Allow DC bus capacitors to discharge.
Model-specific values take priority: These are general reference values. Confirm terminal identification, connector pinout and expected readings in the service manual for the exact indoor and outdoor model before condemning a component.

1. Communication and signal tests

Indoor-to-outdoor serial signal

Measure DC voltage between terminal 2 (neutral) and terminal 3 (signal). To separate indoor and outdoor signals, disconnect terminal 3 and test each side independently. Cross-check from both ends before concluding the interconnecting cable or PCB is faulty.

Model groupIndoor signalOutdoor signal
AST and ART/C60–120 V DC60–120 V DC
ASTA and ASTB40–90 V DC40–90 V DC
ASTGApprox. 200 V DC static3–110 V DC
ARTG and three-phaseApprox. 295 V DC static3–110 V DC

Three-wire remote controller

TestExpected readingInterpretation
Y1 to Y312 V DC; not less than approximately 11.4 V DCController supply. Missing voltage may indicate a controller-board or wiring fault.
Y3 to Y2Fluctuating 7–11 V DC pulseCommunication pulse at the controller terminals.
Y3 to disconnected Y2 cableFluctuating 7–11 V DC pulseCommunication pulse from the indoor unit.

2. Typical outdoor PCB voltage checks

CircuitTypical readingNotes
Main PCB DC input330–370 V DCHigh-voltage DC bus supply.
Outdoor fan motorRed–black: 330–370 V DC
White–black: 15 V DC
Do not unplug the motor while energised.
EEV coil supply12 V DCCheck only using the applicable model procedure.
Thermistor supply5 V DCReturn voltage varies with temperature.
High-pressure sensor supply5 V DCReturn voltage corresponds to pressure.
Reversing-valve solenoid240 V ACShown energised in heating mode on the reference PCB.

3. Power conversion and inverter components

ACTPM active filter module — power OFF

Disconnect all control harnesses and measure resistance on auto-range. A shorted ACTPM may trip the supply circuit breaker.

Black leadRed leadExpected
+360 kΩ
L1360 kΩ
L2Over 1 MΩ
N0 Ω
+P720–900 kΩ
NP360–540 kΩ

IPM / transistor PCB — power OFF, diode mode

Black leadRed leadExpected
PU0.4 V
V0.4 V
W0.4 V
U / V / WN0.4 V each
PN0.7–0.9 V
NPOL

Bridge rectifier

Test conditionExpected reading
Single-phase, power OFF, diode mode+ to each AC terminal: 0.4 V; each AC terminal to −: 0.4 V; + to −: 0.7–0.9 V; reverse − to +: OL.
Three-phase, power ONL1–L2, L2–L3 and L1–L3: 400–415 V AC. Each phase to neutral/earth: 230–240 V AC. DC − to +: 560–600 V DC.
Three-phase, power OFF, diode mode+ to each AC phase: 0.4 V; each AC phase to −: 0.4 V; + to −: 0.7–0.9 V; reverse − to +: OL.

4. DC brushless fan motor — power OFF

Do not disconnect the fan motor while power is applied. The motor contains an internal electronic circuit and operates from a high-voltage DC supply.
Red leadBlack leadExpected
RedBlackOL
WhiteBlack0.5–1.8 V
BlackRed0.8–1.1 V
BlackWhite0.4–0.6 V

Also check that the shaft rotates freely and is not partially or fully seized. Older motors may read near 0.5 V from white to black, while newer motors may read near 1.8 V.

5. Thermistors and pressure transducers

Thermistor testing

  • Power ON: one side of the thermistor circuit should have approximately 5 V DC to DC ground. The return side should be below 5 V DC and varies with temperature.
  • Power OFF: unplug the thermistor and measure resistance in kΩ. Compare bulb temperature, resistance and return voltage with the model-specific chart.
  • Inspect the bulb and cable for damage and test for a short to earth.
Thermistor at 20°CResistanceReturn voltage
Room temperature12.535 kΩ2.219 V DC
Indoor heat exchanger62.905 kΩ2.212 V DC
Discharge temperature64.501 kΩ0.839 V DC
Compressor temperature62.550 kΩ0.860 V DC
Outdoor heat exchanger6.100 kΩ2.189 V DC
Outdoor ambient12.643 kΩ3.759 V DC

Pressure transducer

Power ON: red to black should be approximately 5 V DC. Black to white is the return voltage. As an approximate example, a 2.8 V DC discharge-pressure return corresponds to about 2875 kPa.

Black leadRed leadPower-OFF diode reading
BlackWhite1.0–1.1 V
BlackRed1.2–1.3 V
WhiteRed1.6–1.7 V
WhiteBlack0.6–0.7 V
RedBlack0.5–0.6 V
RedWhite0.6–0.7 V
EarthRed / white / blackOL

6. Electronic expansion valve coil tests — power OFF

Coil typeTest pairsExpected
5-wire, 12 VRed to white, orange, yellow and blue45–50 Ω each
6-wire, 12 VRed to white and orange; brown to yellow and blue45–50 Ω each
J-series high-resistance 6-wireRed to white and orange; brown to yellow and blue150 Ω each; blue–yellow and orange–white approximately 300 Ω
All coil types to earthEvery conductor to earthOL

Inspect for corrosion beneath the coil and confirm the coil is correctly located and firmly clipped to the valve body.

7. Multi-head inverter signal chips

Black leadRed leadExpected resistance
NeutralSignal A1.5–2 MΩ
Signal B1.5–2 MΩ
Signal C1.5–2 MΩ
Signal D1.5–2 MΩ

8. Outdoor-board test run

Where the wall controller is unavailable, some models allow a test run to be initiated from the outdoor LED display board. Use the switch sequence and LED interpretation in the service manual for the exact model.

Return control after testing: Stop the test run from the outdoor display board when testing is complete. Outdoor-board test operation overrides the wall controller until it is cancelled.

9. Diagnostic workflow

  1. Record the complete indoor and outdoor model numbers, serial numbers and fault history.
  2. Confirm the supply voltage, earthing, phase condition and protective devices.
  3. Inspect boards, harnesses and connectors for heat damage, moisture, corrosion or loose connections.
  4. Use the exact meter mode and lead polarity shown for the test.
  5. Compare all readings with the applicable service manual, not one isolated reading.
  6. Confirm related loads are not shorted before fitting a replacement PCB.
  7. After repair, restore all covers and earth connections, then complete a controlled test run.
Important: A correct static component reading does not prove the entire system is operating correctly. Continue diagnosis where supply, communication, mechanical or load-related faults remain possible.