Summary
UTY-VMGX is a Modbus-RTU to Fujitsu VRF network converter that allows a Modbus master (BMS/PLC) to monitor and control VRF indoor units. One converter can supervise up to 128 indoor units. This guide covers capabilities, wiring, addressing, DIP settings, commissioning, and troubleshooting. No links.
Applies to
Fujitsu VRF systems using the FGL (VRF network)
Modbus RTU (RS-485) integrations for building management systems
Core capabilities
Protocol bridge: VRF network (FGL) ↔ Modbus-RTU (RS-485).
Scale: Up to 128 indoor units per converter; multiple converters can share a VRF network.
Control & feedback: Read/write key points (on/off, mode, setpoint, fan, faults) while wired/IR remotes remain usable.
Power: 230 V AC supply to the converter.
System topology
VRF side: Connect to the VRF communications trunk shared with indoor/outdoor units.
Modbus side: Converter is a slave on an RS-485 trunk with a single Modbus master.
Grounding: Bond earth as per panel practice; avoid ground loops between systems.
RS-485 wiring (Modbus side)
Terminations: Enable termination at both ends only of the trunk.
Polarity: Terminals are COM / D- / D+. Keep polarity consistent across all devices.
Shielding: If using shielded cable, earth the shield at one end only. Do not bond shield to COM.
Length & layout: Trunk up to ~1000 m; avoid long stubs; use repeaters for large device counts.
Modbus communications settings (DIP SET6)
Baud rate: 9600 bps (default) or 19200 bps.
Parity: Even (default) or Odd. If Stop = 2, parity is None.
Stop bits: 1 (default) or 2.
Mode: Use Modbus-RTU (ASCII not used).
Match these to the master; document the settings on the panel label.
Addressing
VRF network address (SET1): Unique converter address on the VRF network. Avoid collisions with central controllers or other converters.
Modbus slave address (SET4/SET5): 1…247 recommended. Keep a register mapping sheet with the physical device label.
Indoor unit registration (mapping)
There are three supported methods:
Use defaults
Pre-mapped addresses; suitable for simple systems.
Automatic scan (SET2-4)
Turn SET2-4 ON to start scanning; indoor units will briefly stop while addresses are discovered.
LED display cycles the count of detected indoor units.
Turn SET2-4 OFF to save. Power-cycle to finalise.
PC tool method
Use the configuration utility to read/write registered data. Power must be OFF during a write.
Tip: If multiple converters are on the same VRF network, power only the target refrigerant system during each scan to avoid cross-registration.
Test run & verification
Normal LED state after init: steady green indicators for power and run.
Test run (SET2-3): Turn ON to command a timed test across registered indoor units (auto-ends or turn OFF to stop).
BMS check: From the Modbus master, poll a small set (e.g., first 10 indoors) to confirm address mapping, on/off, mode, setpoint and fault status.
Installation cautions
Install the converter indoors in a clean, dry, ventilated location.
Provide strain relief on all cables; maintain bend radius and separation from mains.
Do not mount with cables exiting directly downward into the enclosure where water could track.
Quick commissioning checklist
VRF trunk connected; converter VRF address unique.
RS-485 polarity correct; termination only at the two ends of the trunk.
Baud / parity / stop match the master.
Modbus slave address recorded on the panel.
Scan or mapping completed; indoor count matches as-built.
BMS reads/writes confirmed (on/off, mode, setpoint, fan).
Final LED state normal; test run completed (if used).
As-built register map filed with the O&M.
Troubleshooting
No response to polls: Verify baud/parity/stop, slave address, terminations, and shield earthing at one end only.
Wrong indoor count / addressing errors: Re-run scan with only the intended system powered; confirm total ≤128; correct any duplicate VRF addresses.
Intermittent data: Reduce stub lengths, tighten terminals, check supply stability to the converter, and confirm the master’s poll rate isn’t saturating the bus.
VRF comms alarms: Check converter VRF address conflicts and wiring polarity on the VRF side; power-cycle after mapping changes.
Modbus fundamentals (for BMS engineers)
Modbus-RTU is master/slave; only one talker at a time.
Keep poll rates conservative; allow enough interval for the converter to traverse the VRF network and update data.
Group reads/writes by contiguous registers to minimise bus traffic.
Key takeaways
UTY-VMGX provides a clean bridge between VRF and Modbus-RTU with capacity up to 128 indoors.
Correct RS-485 practice, unique addresses, and a verified scan/map are the critical success factors.
Validate with a short BMS script before handing over to operations.