Fujitsu Airstage Technical Support

Component Testing - Technician Quick Reference

Diagnostic test procedures for electrical fault isolation and component verification in Fujitsu inverter and standard air conditioning systems.

Electrical safety warning

Testing must only be completed by appropriately qualified technicians. Isolate the power supply before resistance or diode testing. Live-voltage testing exposes the technician to hazardous voltages, including DC bus voltages up to 380 V DC.

Purpose

This guide provides a structured overview of diagnostic test procedures for key components. It is intended as a quick reference for technicians performing on-site electrical testing, fault isolation and verification of component operation.

Before testing

  • Confirm whether the test is a power-off resistance/diode check or a power-on voltage check.
  • Verify readings against ambient temperature, particularly for thermistors and motors.
  • Use model-specific service data where available.
  • Cross-check unexpected readings using the Mobile Technician App.

Quick reference values

ComponentTestExpected reading
Diode bridgeDiode testApprox. 0.4 V per diode; 0.7-0.9 V between + and -
Active Filter Module (ACTPM)Resistance360 kΩ-900 kΩ between terminals
Intelligent Power Module (IPM)Diode test by phase0.4 V ± 0.1 V per phase
DC brushless fan motorDiode testWhite-to-black: 0.5-1.8 V; black-to-red: 0.8-1.1 V
AC fan motorPhase resistanceTypically 5-20 Ω; use the fan-specific table
Pressure transducerPowered voltage test5 V DC supply; 0.5-4.5 V return proportional to pressure
EEV coil - standardResistance45-50 Ω between control wires
EEV coil - J SeriesResistanceApprox. 150 Ω per winding

1. Signal communication tests

Use signal testing to verify communication between indoor and outdoor units and to assess the three-wire remote controller circuit at terminals Y1, Y2 and Y3.

  • Check the system signal between the indoor and outdoor units.
  • Check the three-wire remote controller signal at Y1, Y2 and Y3.
  • Compare measured DC serial communication voltages with the applicable indoor and outdoor circuit data.

2. Power conversion and drive components

Diode bridge - single-phase and three-phase

The diode bridge converts the incoming AC supply to DC voltage.

  • Expected forward voltage drop: approximately 0.4 V per diode.
  • Expected reading between the positive and negative terminals: 0.7-0.9 V.

Active Filter Module (ACTPM)

The ACTPM improves power factor and supplies the DC bus to the inverter.

  • Expected resistance between terminals: 360 kΩ-900 kΩ.

Intelligent Power Module (IPM)

The IPM drives the compressor windings at U, V and W.

  • Expected diode reading: 0.4 V ± 0.1 V per phase.

3. Fan motor testing

DC brushless fan motors

These motors operate with approximately 330-380 V DC main power and 15 V DC control power.

  • White-to-black diode reading: 0.5-1.8 V.
  • Black-to-red diode reading: 0.8-1.1 V.

AC fan motors

Check resistance across the phases and compare the result with the fan-specific table. A typical range is 5-20 Ω.

4. Sensor testing

Thermistors

Test conditionMethod and expected result
Power onExpect a 5 V DC supply and a lower return voltage that varies with temperature.
Power offMeasure resistance and compare it with the applicable thermistor table or the Mobile Technician App.

Pressure transducer

  • Expected supply between red and black: 5 V DC.
  • Expected return signal: 0.5-4.5 V, proportional to system pressure.

5. Electronic Expansion Valve (EEV) coil testing

  • Five-wire and six-wire coils: 45-50 Ω between control wires.
  • J Series high-resistance coils: approximately 150 Ω per winding.
  • Coil-to-earth test: O/L is expected.

6. Thermistor reference at 20°C

SensorReference resistance
Room temperature thermistor12.5 kΩ
Heat exchanger thermistor62.9 kΩ
Compressor thermistor62.5 kΩ

A typical thermistor signal voltage at 20°C is 2.1-2.3 V DC.

7. Manual test run from the outdoor display

  1. Use the outdoor LED display board to start a manual test run when wall controller access is unavailable.
  2. After testing, terminate the test run at the outdoor display so control is returned to the wall controller.

Interpreting abnormal readings

Readings outside the expected range may indicate a shorted diode, open circuit, failed component or PCB fault. Confirm the reading, test under the correct power condition and compare it with the applicable model-specific service information before replacing parts.