Overview

R-410A is a high-pressure, HFC-based refrigerant used as a long-term replacement for R-22 in air conditioning and refrigeration systems. It contains no chlorine (ODP = 0), offering an environmentally safer option while delivering higher capacity and efficiency. Because it operates at pressures about 50 % higher than R-22, only systems and tools specifically designed for R-410A may be used

R-410A

.


1. Composition and Properties

  • Chemical composition: 50 % HFC-32 / 50 % HFC-125 (azeotropic blend).

  • Cylinder colour: Rose (Pantone 507).

  • Operating density: ~50 % greater than R-22.

  • Vapour pressure: ~58 % greater at 77 °F.

  • Toxicity and flammability: Rated A1/A1 under ASHRAE—lowest risk category for toxicity and flammability

    R-410A

    .


2. Typical Operating Pressures

At an outdoor ambient temperature of 95 °F, a high-efficiency condensing unit will typically show:

RefrigerantSuction (Low-Side)Discharge (High-Side)
R-22≈ 68 psi≈ 250 psi
R-410A≈ 118 psi≈ 400 psi

R-410A pressures are roughly 50–70 % higher than R-22, and service tools, hoses, and recovery cylinders must therefore be rated for at least 400–750 psi working pressure

R-410A

R-410A

.


3. Pressure–Temperature Relationship

Table 1 on page 6 of the document provides a full chart. Below are key reference points for normal system diagnostics:

Saturation Pressure (psig)Temperature (°F)Application
11839 °FTypical low-side at 95 °F ambient
20069 °FEvaporator mid-range
318100 °FCondensing ~100 °F
400117 °FTypical head pressure at 95 °F ambient
500134 °FHigh head, hot day
600149 °FMaximum safe high-pressure limit

A typical operating suction temperature for comfort-cooling will be around 40 °F (suction ≈ 118 psi), with discharge pressures normally ranging 380–440 psi depending on outdoor temperature and coil condition

R-410A

.


4. System Components and Lubrication

  • Use POE (polyol-ester) oil only—highly hygroscopic; keep sealed until installation.

  • Do not use R-22 TXVs or filter-driers rated below 600 psi.

  • Compressors, coils, and expansion devices must be specifically designed for R-410A due to its higher pressure and mass flow characteristics.


5. Safety and Handling

  • Systems may operate above 600 psi without tripping the safety switch; some high-pressure cut-outs are set at 610 psi (reset ≈ 420 psi)

    R-410A

    .

  • Always wear eye and hand protection—liquid contact can cause frostbite.

  • R-410A is heavier than air and can displace oxygen in confined spaces; ensure proper ventilation.

  • Cylinders must never exceed 125 °F (52 °C) and must be stored upright.

  • Charge as liquid only to prevent fractionation of the blend.


6. Recovery and Re-Use

  • Never vent R-410A to the atmosphere.

  • Only use DOT 4BA400 or 4BW400 recovery cylinders (rated ≥ 400 psi).

  • Dedicated manifold gauges and hoses should be clearly marked for R-410A to prevent cross-contamination with other refrigerants

    R-410A

    .


7. Installation and Service Notes

  • Manifold gauges: 750 psi (high side) / 200 psi (low side) with 500 psi retard.

  • Hoses: 750 psi service pressure minimum.

  • Always braze joints—do not use low-temperature solder.

  • Evacuate systems to ≤ 500 microns before charging.

  • Use a liquid-line filter-drier rated ≥ 600 psi.


8. Phase-Out of R-22 and Adoption of R-410A

  • 2010: End of production of new R-22 equipment.

  • 2020: End of R-22 manufacture; only reclaimed R-22 permitted.
    R-410A is now the industry standard for residential and light commercial systems

    R-410A

    .


Summary

R-410A delivers 5–6 % higher EER, compact equipment design, and zero ozone impact but demands strict adherence to pressure-rated tools, correct oil management, and liquid-charging procedures. Typical diagnostic pressures are ~120 psi suction and ~400 psi head at 95 °F ambient.

Following these practices ensures safety, efficiency, and compliance with current refrigerant standards.