General Assist Technical Reference

Wall Hung Split Defrost Operation

Conditions for starting and completing automatic defrost
Technical overview of outdoor coil temperature and compressor runtime logic during heating operation
During heating operation, moisture can freeze on the outdoor heat exchanger. The system automatically monitors the outdoor coil temperature and compressor operating time, then starts a defrost cycle when the programmed conditions are met.
Normal operation: During defrost, the indoor fan may stop, heating output will pause and steam or water may be visible around the outdoor unit. This is expected and does not normally indicate a fault.

1. Conditions for starting defrost

Defrost begins when the outdoor heat exchanger temperature sensor, identified as Tn, detects a sufficiently low coil temperature after the required compressor operating time.

Operation stageCompressor integrating operation timeCondition to start defrost
First defrost after start-upLess than 22 minutesDefrost does not operate
22 to 62 minutesTn ≤ -9°C
More than 62 minutesTn ≤ -5°C
Second and subsequent defrost operationsLess than 35 minutesDefrost does not operate
More than 35 minutes(Tn - Tn10) ≤ -5°C and (Tn - Tnb) ≤ -2°C, with Tn ≤ -6°C
Integrating defrost / constant monitoringMore than 240 minutes of long continuous operationTn ≤ -3°C
More than 215 minutes of extended continuous operationTn ≤ -5°C
Less than 10 minutes of intermittent operationDefrost begins after 40 compressor OFF counts
Intermittent operation note: When continuous compressor operation is less than 10 minutes, the control uses compressor OFF counts to determine when defrost is required. The OFF count resets after a defrost cycle occurs.

2. Conditions for completing defrost

The defrost cycle ends when either of the following release conditions is met:

Defrost release condition
The outdoor heat exchanger temperature sensor value, Tn, rises above +13°C.
The compressor has operated in defrost for more than 15 minutes.
Once a release condition is reached, the system exits defrost and automatically resumes normal heating operation. A short delay may occur while refrigerant pressures stabilise and the indoor coil warms.

3. Technical terms

TermMeaning
TnCurrent outdoor heat exchanger temperature sensor reading.
Tn10Outdoor heat exchanger temperature measured after 10 minutes of continuous operation.
TnbAverage outdoor heat exchanger temperature over the previous five minutes.
Integrating operation timeAccumulated compressor operating time used by the controller when assessing frost formation.

4. What customers may notice

  • Heating temporarily stops while the outdoor coil is defrosted.
  • The indoor fan may stop or operate at a very low speed to prevent cool air entering the room.
  • The outdoor fan may stop during part of the cycle.
  • Water may drain from the outdoor unit as frost melts.
  • Steam or mist may appear around the outdoor unit, particularly in cold and humid weather.
  • The complete interruption can last several minutes before heating resumes.
Further investigation may be required if the system remains in defrost for unusually long periods, repeatedly defrosts with very short heating intervals, does not return to heating, displays an error code, or the outdoor coil remains heavily iced after the cycle.

5. Summary

The defrost control continuously assesses outdoor coil temperature, temperature change and compressor operating time. Defrost is only initiated when the applicable temperature and runtime conditions are met. The cycle finishes when the outdoor coil warms above +13°C or when the 15-minute maximum compressor time is reached, after which the system returns to heating automatically.