Overview
The Service Mode on the UTY-RVNYN wired remote controller allows technicians to configure key system settings such as operation mode exemptions, temperature range limits, and temperature sensor correction.
All operations must be performed within 3 minutes after power-up.
1. Entering Service Mode
Access the Service Menu
Press the [Menu] button twice while the “Monitor” screen is displayed to enter the Submenu.
Press and hold both [Left] and [Right] Screen Switch buttons simultaneously for 5 seconds.
→ The display switches to the “Service” screen.
Activate R.C. Function Setting
Press [Left Screen Switch] + [Enter] + [Down Cursor] simultaneously for 5 seconds.
Note: Apply consistent pressure; pressing too hard may prevent detection.The screen changes to “R.C. Function Setting.”
2. Service Mode Configuration Options
(a) Operation Mode Exemption
Allows removal of specific operation modes (e.g., “Dry,” “Heat”) from the controller’s user menu.
(This does not disable the mode at the indoor unit.)Procedure:
From the “R.C. Function Setting” screen, select Operation Mode Exemption.
Use the cursor to check or uncheck operation modes to be exempted.
Notes:
In dual controller configurations, set the same exemptions for both Primary and Secondary units.
Indoor units retain the last active mode, so memory overwrite is unnecessary after operation.
(b) Set Temperature Range (Initial)
Restricts the available temperature adjustment range for each operation mode.
Procedure:
Select Set Temp. Range (Initial) from the list.
Adjust the upper and lower temperature limits for each operation mode (Cooling, Heating, Auto).
Confirm settings with [Enter].
Notes:
Apply the same range on both controllers if dual control is used.
Once set, the temperature range remains fixed until reconfigured.
(c) Room Temperature Correction
Adjusts the displayed room temperature to match actual conditions, compensating for sensor deviation.
Procedure:
Select Room Temp. Correction.
Adjust the correction value (e.g., ±2°C) using the cursor buttons.
Confirm by pressing [Enter].
Recommendation:
Use a calibrated thermometer at sensor height to verify and fine-tune accuracy.
3. Important Notes
Perform all operations within 3 minutes after turning on power.
All adjustments made in Service Mode are stored automatically upon confirmation.
In dual controller setups, always set both controllers to the same parameters to ensure consistent operation.