1. System Overview

The wired remote controller system allows up to two controllers to be connected to a single indoor unit — designated as Primary and Secondary controllers.
However, when multiple indoor units are grouped, up to 16 indoor units can be controlled using one or two remote controllers.
A third wired remote controller connection is not supported and is considered prohibited.


2. System Diagram

Single Remote Controller Connection

  • One wired controller connects directly to the indoor unit.

  • Cable “A” represents the communication link (remote controller cable).

Indoor Unit ─── A ─── Remote Controller

Dual Remote Controller Connection

  • Two wired controllers (Primary and Secondary) connect in parallel to the indoor unit.

  • Cables “B” and “C” represent the communication lines.

Indoor Unit ─── B ─── Primary Controller └── C ─── Secondary Controller

Note: Only two controllers can be connected per indoor unit.
Connection of three controllers is not permitted.


3. Controller Combination Rules

Permitted Combinations

Indoor Unit TypePrimary ControllerSecondary Controller
Any unitUTY-RVN*M + UTY-RVNYN
Any unitUTY-RVN*M + UTY-RNN*M
Any unitUTY-RVN*M + AR-WAE***, AR-CTE*** (Accessory)

Prohibited Combination

Indoor Unit TypeController TypeStatus
Any unitAR-3TA*** (Accessory) used with UTY-RVN*M or UTY-RVNYNNot Allowed

*Asterisk () indicates model variations.*


4. Group Control (Multi-Indoor Configuration)

Up to 16 indoor units can be controlled simultaneously with 1 or 2 wired controllers connected in a group configuration.

Example:

Remote Controller ─── Indoor 1 ─── Indoor 2 ─── Indoor 3 ─── ... ─── Indoor 16

All indoor units are connected using a polar 3-core remote controller cable, maintaining correct polarity and daisy-chain configuration.


5. Installation Notes

  • Maintain proper polarity across all communication terminals.

  • Use only approved remote controller cables as specified in the wiring standards section.

  • Do not mix incompatible controller models in the same network.

  • A maximum cable length and resistance per total system must follow manufacturer limits.

  • Three wired controllers connected to one indoor unit is strictly prohibited.