AIRSTAGE Technical Reference

Remote Controller Cable Requirements

Cable selection and installation guidance for UTY-RVN*M and UTY-RVNYN remote controllers
Important: All wiring must be completed by appropriately qualified personnel and comply with applicable local electrical codes and regional cable standards.

1. Cable requirements

UseCable sizeWire typeApplicable modelRemarks
Remote controller cable0.33 mm² (22 AWG)Polar 3-coreUTY-RVN*MUse sheathed PVC cable.
UTY-RVNYNUse shielded cable, field supplied, in accordance with regional cable standards.

2. Installation notes

1Ensure all wiring complies with local electrical codes and standards.
2Maintain correct polarity across all 3-core connections between the indoor unit and remote controller.
3Do not run communication cables parallel to power supply cables. This helps reduce the risk of electrical noise interference.
4Keep the total communication cable length within the manufacturer-specified limits.
Installation check: Before energising the system, verify cable type, conductor size, polarity, terminal security and cable routing.
Remote controller cable installation reference