1. Purpose

The defrost control logic automatically manages outdoor coil frost removal to maintain heating performance and efficiency.
This document explains the conditions for defrost initiation and completion, enabling service technicians to assess normal operation or identify control faults.


2. Conditions for Starting Defrost Operation

The outdoor unit initiates a defrost cycle based on compressor runtime and outdoor heat exchanger temperature.
The control sequence varies depending on whether it is the first, subsequent, or integrating (continuous monitoring) defrost.


2.1 First Defrost after Start-Up

Compressor Integrating Operation TimeConditionOutdoor Heat Exchanger Temperature
Less than 22 minutesDoes not operate
22–62 minutesDefrost starts if below –9°C
More than 62 minutesDefrost starts if below –5°C

Summary:
During initial operation, the unit waits until sufficient runtime and low outdoor coil temperature confirm frost accumulation.


2.2 Second and Later Defrost Cycles

Compressor Integrating Operation TimeConditionOutdoor Heat Exchanger Temperature
Less than 35 minutesDoes not operate
More than 35 minutesDefrost starts if below –10°C

Summary:
Subsequent defrosts require a longer compressor runtime and lower coil temperature, ensuring efficient operation without unnecessary defrosting.


2.3 Integrating Defrost (Continuous Monitoring Mode)

Compressor Integrating Operation TimeConditionTrigger
More than 240 minutes (continuous)Coil temperature below –3°C
Less than 10 minutes (intermittent)Compressor OFF count = 40 times

Notes:

  • If the compressor operates for less than 10 minutes repeatedly, the controller accumulates the OFF count.

  • When the count reaches 40, the defrost cycle is forced to start.

  • After any defrost operation, the OFF count is reset to zero.


3. Conditions for Defrost Termination

Defrost concludes automatically once either of the following release conditions is met:

Release ConditionDescription
Outdoor heat exchanger temperature ≥ 12°CCoil temperature sufficiently high; frost melted.
Compressor operation time ≥ 15 minutesSafety timeout to prevent over-defrosting.

Summary:
The system ensures reliable defrost completion while preventing excessive downtime that could reduce heating capacity.


4. Field Service Notes

  • Normal Defrost Cycle Duration: Typically between 5–12 minutes, depending on ambient conditions.

  • Indicators: During defrost, the outdoor fan stops, and compressor continues operating — indoor unit may reduce air delivery.

  • Common Symptoms of Faulty Defrost Control:

    • Prolonged heating loss at low ambient temperature.

    • Outdoor coil remaining frozen.

    • Frequent or premature defrost cycles.

Diagnostic Tip:
If the unit fails to defrost, check:

  1. Outdoor thermistor readings (resistance vs. temperature chart).

  2. Compressor cumulative runtime and OFF count behavior.

  3. PCB logic compliance with the above temperature/time thresholds.


5. Technician Summary Table

Cycle TypeCompressor RuntimeOutdoor Coil Temperature TriggerRelease Condition
1st Defrost>22 min (–9°C) / >62 min (–5°C)Below thresholdCoil ≥ 12°C or 15 min elapsed
2nd+ Defrost>35 minBelow –10°CCoil ≥ 12°C or 15 min elapsed
Integrating>240 min or 40 OFF countsBelow –3°CCoil ≥ 12°C or 15 min elapsed

6. Practical Service Guidance

  • Defrost intervals typically occur every 30–90 minutes depending on load and ambient.

  • When investigating abnormal defrost behavior, always verify:

    • Thermistor calibration (frost sensor at coil).

    • Compressor runtime logic (check via error history or control board diagnostics).

    • Outdoor fan relay operation (must stop during defrost).