1. Document Overview
The guide lists compatible indoor/outdoor models across ARTG, ARTA, ARTC, ARXB, ARXA, and ARXC series, specifying:
Static pressure modes
Recommended static pressure range (Pa)
Supply and return air connection dimensions
Optional duct connection kits (UTD-RF204, UTD-SF045T)
This document serves as a field installation and commissioning reference to ensure correct airflow matching and physical duct sizing between indoor and outdoor units
Fujitsu General Ducted Connecti…
.2. Key Models and Specifications
ARTG Reverse Cycle High Static Ducted – Single Phase (New)
| Indoor Model | Outdoor Model | Static Modes | Pressure Range (Pa) | Supply Air (mm) | Return Air (mm) |
|---|---|---|---|---|---|
| ARTG45LDTA | AOTG45LBTA | 20 | 60–250 | 1162 × 277 | 1295 × 316 |
| ARTG54LDTA | AOTG54LBTA | 20 | 60–250 | 1162 × 277 | 1295 × 316 |
| ARTG60LDTA | AOTG60LBTA | 20 | 60–250 | 1162 × 277 | 1295 × 316 |
Notes (Field Application):
Designed for high static commercial duct applications.
Factory-configured static range allows for multiple branch duct layouts or higher filtration resistance.
Use UTD-RF204 and UTD-SF045T for optimal transition and balance during airflow measurement
Fujitsu General Ducted Connecti…
.
ARTG / ARTC Reverse Cycle High Static Ducted Inverter – Three Phase
| Indoor Model | Outdoor Model | Pressure Range (Pa) | Supply Air (mm) | Return Air (mm) |
|---|---|---|---|---|
| ARTC72LATU | AOTA72LALT | 50–250 | 1200 × 350 | 1251 × 370 |
| ARTC90LATU | AOTA90LALT | 50–250 | 1200 × 350 | 1251 × 470 |
Application Notes:
Used in large commercial multi-room ducted systems.
Three-phase units with high static capability (up to 250 Pa) for long duct runs.
Supports external control features (Low Noise / Peak Cut / Error Output) as detailed in separate service documents.
ARTA Reverse Cycle Slimline Ducted Inverter – Single Phase
| Indoor Model | Outdoor Model | Pressure Range (Pa) | Supply Air (mm) | Return Air (mm) |
|---|---|---|---|---|
| ARTA30LBTU | AOTA30LBTL | 30–150 | 1015 × 240 | 1015 × 240 |
| ARTA45LATU | AOTA45LBTL | 30–150 | 1015 × 240 | 1015 × 240 |
Notes:
Slimline chassis for restricted ceiling cavities.
Medium static pressure range ideal for short duct runs.
3. Inverter Multi – ARTG Bulkhead Ducted Units
| Indoor Model | Outdoor Model | Static Range (Pa) | Supply Air (mm) | Return Air (mm) |
|---|---|---|---|---|
| ARTG09LLLB | AOTG09LBCA | 0–90 | 650 × 151 | Bulkhead |
| ARTG18LLTA | AOTG18LACC | 0–90 | 850 × 151 | Bulkhead |
Purpose:
Low static, compact bulkhead systems for concealed bedroom or apartment applications.
Field Tip:
Ensure condensate drain and airflow direction match ceiling cavity layout — these units are often factory left-hand drain convertible to right-hand.
4. VRF and Commercial System Compatibility (Page 2)
For VRF and multi-indoor systems:
VRF Bulkhead (ARXB) models support 0–50 Pa.
VRF High Static (ARXC) models support 100–300 Pa.
VRF Slimline (ARXA) models support 30–150 Pa with identical duct connection kits (UTD-RF204 / UTD-SF045T)
Fujitsu General Ducted Connecti…
.
5. Service Application Notes
Static Pressure Tuning:
Adjustable fan speed modes allow field calibration using a manometer to achieve recommended static within table range.Transition Ducts:
Always use UTD-RF204 (return) and UTD-SF045T (supply) when adapting to non-standard ductwork to prevent turbulence and maintain rated capacity.Replacement Check:
For system retrofits, confirm compatibility of physical duct sizes and electrical phase (single/three-phase) before unit replacement.Commissioning:
Measure ESP (External Static Pressure) at both supply and return to confirm operation within recommended range for optimal airflow and noise performance.
6. Quick Reference Summary
| Series | Type | Static Range (Pa) | Phase | Optional Kits |
|---|---|---|---|---|
| ARTG | High Static | 60–250 | Single | UTD-RF204, UTD-SF045T |
| ARTA | Slimline | 30–150 | Single | UTD-RF204, UTD-SF045T |
| ARTC | High Static | 50–250 | Three | UTD-RF204, UTD-SF045T |
| ARXB | Bulkhead | 0–50 | — | — |
| ARXA | Slimline | 30–150 | — | UTD-RF204, UTD-SF045T |
| ARXC | High Static | 100–300 | — | — |