General Assist Technical Reference

Outside Air Handling Unit

Electrical system configuration, component checks and fault diagnostics
For Fujitsu Outside Air Handling Unit commissioning, maintenance and troubleshooting
This article explains the five main sections of the OAU electrical control system and provides expected voltages, resistance values and inspection points for field diagnosis.
Electrical safety: Work must only be completed by appropriately qualified personnel. Isolate the unit before resistance or continuity testing and confirm the DC bus has discharged before touching electrical components.

1. System overview

The OAU electrical control system is divided into five main sections:

SectionPrimary purpose
Filter circuitSurge protection, noise suppression and incoming supply protection
Converter and smoothing circuitConverts 230 V AC to approximately 325 V DC and smooths the DC bus
Power supply circuitProduces low-voltage DC supplies for motors, relays and control electronics
Controller circuitControls refrigerant components, sensors and system communication
Switch PCB and auxiliary componentsAddressing, function settings and connection of field components

2. Filter circuit

Components: Filter PCB, 20 A and 3.15 A fuses, varistor, surge absorber, common-mode choke coil and capacitors.

  • Protects internal circuits from incoming electrical noise and voltage surges.
  • Prevents inverter-generated noise from feeding back into the mains supply.
  • Provides overvoltage and surge protection through the varistor and surge absorber.
ComponentSpecification
Common-mode choke coil20 A, 2 mH
X capacitorAC 275 V, 1.0 µF
Y capacitorAC 250 V, 0.01 µF
VaristorAC 470 V
Surge absorberAC 3000 V
Fuse 120 A
Fuse 23.15 A
Inspection: Check continuity across both fuses and measure approximately 230 V AC between W305 and W306. If a fuse is open, inspect for short-circuited components in the primary or solenoid relay circuit before replacement.

3. Converter and smoothing circuit

Components: Diode bridge, smoothing capacitor, posistor and reactor.

  • Converts 230 V AC to approximately 325 V DC.
  • Reduces DC voltage ripple using a high-capacity capacitor.
  • Limits inrush current through the posistor, which is a PTC thermistor.
  • Uses the reactor to improve power factor and reduce harmonic distortion.
Component5-8 HP10 HP
Diode bridge600 V / 15 A600 V / 25 A
Capacitor450 V / 1000 µF450 V / 1200 µF
Reactor8 A / 13 mH14 A / 6 mH
Posistor300 Vrms / 12 ArmsNot listed

Inspection points

  • Diode bridge output should be approximately 325 V DC from a 230 V AC supply.
  • The capacitor must not show bulging, leakage or deformation.
  • Posistor resistance should be approximately 40 Ω ±25% at 25°C.
  • The reactor must have continuity and must not be open circuit.

4. Power supply circuit

The power supply PCB converts the high-voltage DC bus into low-voltage DC supplies for the control and motor circuits.

OutputApplication
15 V DCMotor control
12 V DC / 5 V DCRelays, wired remote controller and controller PCB

Protective fuse: 3.15 A / 250 V, protecting the power supply IC and primary circuit.

No DC output: Confirm approximately 325 V DC is present at connector C600, then check primary and secondary voltages around the switching power supply IC.

5. Controller and communication circuits

Controller PCB

  • Manages the refrigerant cycle, including EEV, SV21 and compressor control signals.
  • Collects thermistor data for heat exchanger and air-temperature control.
  • Interfaces with remote controllers and the outdoor unit.

Communication PCB

  • Handles communication between indoor, outdoor and RB units.
  • Provides system error reporting through the wired remote controller.
Inspection pointExpected condition
CN412 V DC / 5 V DC supply to controller PCB
CN8 / CN95 V DC supply for thermistor sensors
Green LEDLED on indicates normal microprocessor operation

6. Switch PCB and peripheral components

The switch PCB is used to configure refrigerant addresses, remote controller settings and other function settings. DIP switches adjust functions, while rotary switches assign address numbers.

ComponentExpected value or check
Fan motors - 5, 8 and 10 HPResistance between pins 4 and 6: 300 kΩ or greater
Electronic expansion valve200 Ω ±10% at 20°C
Solenoid valve SV211324 Ω at 20°C
ThermistorsCompare against the applicable temperature/resistance table; example: approximately 26.3 kΩ at 15°C

7. Fault indication

Error codeDescriptionPossible cause
39.1Motor 1 DC power supply errorLow DC voltage below 163 V or diode bridge fault
39.2Motor 2 DC power supply error - 8 HP onlyLow DC voltage below 163 V or diode bridge fault
4.AAir-temperature thermistor errorSensor open circuit or short circuit
5.9Fan motor errorFan rotation fault or drive-signal fault

8. Recommended diagnostic sequence

  1. Confirm the incoming 230 V AC supply and check both filter-circuit fuses.
  2. Confirm approximately 325 V DC at the converter output and C600 input.
  3. Inspect the smoothing capacitor for swelling, leakage or deformation.
  4. Confirm the required 15 V, 12 V and 5 V DC control supplies.
  5. Check the green controller PCB LED and system communication.
  6. Measure motors, EEV, solenoid valve and thermistors against the listed values.
  7. Use the displayed fault code to focus further testing.
Capacitor warning: Wait at least five minutes after isolating the power supply before touching the capacitor or DC bus components. Confirm the voltage has reduced to a safe level with an appropriate meter before proceeding.
Technical values in this article are based on the supplied OAU electrical parts reference. Always confirm the applicable model documentation and wiring diagram before replacing components.