1) Refrigeration & Heat-Pump Basics
Vapor-compression loop: compressor → 4-way valve → indoor/outdoor heat exchangers → expansion device → accumulator.
The 4-way valve reverses the circuit to provide cooling or heating.
2) Major Components — Purpose & Checks
Compressor: raises pressure/temperature and circulates refrigerant.
Heat exchangers (indoor/outdoor): reject/absorb heat; ensure free airflow and clean fins.
Strainer & capillary/EEV: meters refrigerant; watch for debris or restrictions.
Accumulator: protects the compressor from liquid flood-back.
3) Control & Operating Modes
Modes: Cooling, Heating, Dry, Fan, Auto.
Auto mode selects cooling or heating based on room temperature and setpoint.
Timers (On/Off/Sleep/Program) adjust operation and setpoint trajectories.
4) Indoor Airflow Management
Cooling/Dry: fan speed steps based on room/setpoint delta.
Dry: intermittent indoor-fan operation synchronized with compressor cycling.
Heating: fan ramps with coil temperature to prevent cold draft.
Louvers: default horizontal in cooling/dry and downward in heating; swing ranges vary by model.
5) Room-Temperature Control Logic
Controller compares room temperature (TR) to setpoint (TS) and sequences compressor, outdoor fan, and indoor fan.
Anti-short-cycle timers (typically ~3 minutes) protect the compressor from rapid restarts.
6) Automatic Protections
Anti-icing (cooling): reduces frequency or pauses to avoid indoor-coil freeze.
Heating overload: staged responses as indoor-pipe temperature rises.
Cold-draft prevention: delays/limits indoor fan at heat start-up.
Auto-defrost: frost judgement triggers valve shift and controlled defrost, then resumes heating.
7) Indicator Lamps & Thermistors
Lamp behavior tables classify faults for first-pass triage.
Thermistor reference tables (room/pipe, outdoor coil/ambient, discharge) support bench testing and verification.
8) Troubleshooting Framework
Root-cause domains: operation misuse, environment, installation, maintenance, electrical circuit, and refrigerant system.
No operation / no lights: check supply, fuses, low-voltage rails, reset circuit, and controller inputs.
Indoor fan inoperative: inspect capacitor/coil, bearings, drive components, and controller output.
Outdoor fan inoperative: confirm drive signals and motor health.
Compressor inoperative: verify relays/drives, overloads, terminal voltages, and mechanical condition.
Poor cooling/heating: assess airflow, load, charge, restrictions; use ΔT and pressure reasoning.
Noise/Vibration: check mounting, piping contact, fans/bearings, 4-way valve, compressor mounts.
Water leakage (cooling): check leveling, drain route, trap, and filters.
9) Installation Highlights (Legacy Guidance)
Match capacity to room size; respect maximum line lengths and height differences.
Calculate additional refrigerant charge vs pipe length where required.
Follow flaring/connection procedures and correct flare-nut torque values.
10) Service Best Practices
Respect anti-short-cycle timers before restarting.
Log baseline commissioning data (pressures, ΔT, fan speeds, input current).
Validate thermistors against reference tables before replacing PCBs.
Treat icing/overload and defrost events as normal protective behavior unless persistent under nominal conditions.