Summary
Use this checklist to isolate and resolve a CO communication fault on a wired wall controller. The sequence below verifies power, network integrity, addressing, and component compatibility before replacement is considered.
Applies to
Wired wall controllers on residential/VRF indoor units
Service technicians diagnosing communication (“CO”) alarms
Safety
Isolate mains supply before opening indoor unit panels or handling wiring.
Use insulated probes and measure DC voltages on the correct meter range.
Restore power only when directed for live tests.
Tools
Digital multimeter (V DC, V AC)
Small flathead screwdriver for DIP switches
Controller/indoor PCB part numbers and model labels for cross-checks
Procedure
Confirm controller power
Measure 12 V DC at the wall controller terminals.
If 12 V DC is missing, go to Step 5.
Verify cabling
Confirm screened data cable ~0.33 mm² conductors (commonly called “data cable”).
Check for damage, poor terminations, reversed polarity, or shorts to shield/earth.
Standalone vs networked
Determine if the controller is standalone. If networked, temporarily isolate to standalone for testing, or ensure addressing is correct before proceeding.
DIP switch and address settings
Confirm DIP switch positions on both the wall controller and the indoor control PCB per site design (address/group/mode).
Correct any mismatch.
Upstream power check (if no 12 V DC at controller)
Verify indoor unit mains 240 V AC is present.
Confirm indoor PCB DC supply ~18 V DC (where applicable) feeding the controller regulator.
If upstream power is correct but the controller still lacks 12 V DC, replace the indoor control PCB (or the controller power module as applicable).
Signal integrity (live test)
With power on, measure communication line DC between the wall controller and indoor PCB.
Expect ~7–11 V DC on both sides of the link.
Significant deviation on either side indicates a fault toward that side (controller, cable segment, or indoor PCB interface).
Isolate the weak side and replace as needed
Based on Step 6 readings, replace the component associated with the side showing poor voltage or unstable signal after confirming wiring and terminations.
Part/model compatibility
After any replacement, confirm part numbers and indoor model numbers are a compatible pairing.
Do not rely solely on the error code—verify against parts documentation.
Validate the test method
If all measurements and settings appear correct yet the CO fault persists, re-check probe points, polarity, and meter range. Repeat Steps 1–7 to confirm results.
Reset to clear latched errors
After correcting any issue, power the system OFF for at least 10 minutes to allow full discharge and fault reset before retesting.
Quick decision guide
No 12 V DC at controller → Check 240 V AC & ~18 V DC on indoor PCB → If present, replace indoor PCB power to controller.
7–11 V DC present on both sides but CO remains → Re-check addressing/DIP and cabling; verify compatibility; reset power for 10 minutes.
Asymmetric or out-of-range comm voltage → Fault lies toward the side with poor reading → Inspect/replace that component or cable.
Post-replacement CO → Confirm correct part number and indoor model pairing; re-address and retest.
Technician notes
Keep cable screens continuous and terminated per site standard; avoid sharing with high-noise conductors.
Label addresses at the controller and indoor PCB after final setup to simplify future service.
Document final measurements (12 V DC feed and comm line V DC) on the job card for traceability.