AIRSTAGE Technical Reference

Fujitsu Component Testing

Electrical diagnostic procedures and expected readings
Quick reference for qualified technicians testing inverter and standard air conditioning systems
This guide provides a structured overview of diagnostic test procedures for key components within Fujitsu inverter and standard air conditioning systems. Use it as a quick reference when performing on-site electrical testing, fault isolation and component verification.
Electrical safety: Testing must only be completed by appropriately qualified personnel. Isolate power before resistance or diode tests. Power-on voltage testing involves hazardous voltages, including DC bus voltages up to 380 V DC.

1. Signal communication tests

  • Verify the system communication signal between the indoor and outdoor units.
  • For a 3-wire remote controller, test the signal at terminals Y1, Y2 and Y3.
  • Confirm the expected DC serial communication voltage values at both the indoor and outdoor circuits.
Diagnostic approach: Confirm supply and polarity first, then compare the measured signal against the applicable model documentation. A missing or unstable signal may indicate wiring, connection or PCB issues.

2. Power conversion and drive components

ComponentFunctionExpected reading
Diode bridge
1-phase / 3-phase
Converts the AC supply to DC voltage.Approximately 0.4 V forward voltage drop per diode; 0.7–0.9 V between positive and negative.
Active Filter Module
(ACTPM)
Improves power factor and supplies the DC bus to the inverter.Resistance range: 360 kΩ–900 kΩ between terminals.
Intelligent Power Module
(IPM)
Drives the compressor windings at U, V and W.Expected diode reading: 0.4 V ± 0.1 V per phase.

3. Fan motor testing

Motor typeSupply / testExpected reading
DC brushless motorTypically operates with 330–380 V DC main power and 15 V DC control power.White-to-black: 0.5–1.8 V diode reading.
Black-to-red: 0.8–1.1 V diode reading.
AC fan motorCheck resistance across the motor phases.Refer to the fan-specific table; the typical range is 5–20 Ω.

4. Sensor testing

Thermistors

  • Power on: Expect a 5 V DC supply with a lower return voltage. The return voltage varies with temperature.
  • Power off: Check resistance against the applicable thermistor table or the Mobile Technician App.

Pressure transducer

  • Confirm 5 V DC between the red and black wires.
  • Expected return signal is 0.5–4.5 V DC, proportional to system pressure.

5. Electronic expansion valve coil testing

Coil typeExpected resistanceAdditional check
5-wire / 6-wire coil45–50 Ω between control wires.Test each winding and compare readings for consistency.
J Series high-resistance coilApproximately 150 Ω per winding.Always test the coil to earth; the expected result is O/L.

6. Thermistor quick reference at 20°C

ThermistorTypical resistance at 20°CTypical voltage at 20°C
Room temperature12.5 kΩTypically 2.1–2.3 V DC. Confirm against the applicable sensor table.
Heat exchanger62.9 kΩ
Compressor62.5 kΩ
Thermistor readings are temperature-dependent. Compare the measured resistance with the actual sensor temperature rather than relying on the 20°C reference alone.

7. Manual test run procedure

  1. Where wall controller access is unavailable, activate the manual test run from the outdoor unit LED display board.
  2. Observe system operation and complete the required diagnostic checks.
  3. Terminate the test run from the outdoor display when testing is complete. This returns operating control to the wall controller.

8. Technician notes

  • Always isolate power before performing resistance or diode tests.
  • Verify readings against ambient or component temperature, particularly for thermistors and motors.
  • Cross-check unusual readings using the Mobile Technician App and the applicable model documentation.
  • Abnormal readings may indicate shorted diodes, open circuits, damaged wiring, a failed component or PCB failure.
Important: The values in this article are a quick reference only. Model-specific service documentation takes priority where values or test methods differ.