Purpose
This document provides a structured overview of diagnostic test procedures for key components within Fujitsu inverter and standard air conditioning systems. It serves as a quick reference guide for technicians performing on-site electrical testing, fault isolation, and verification of component functionality.
Contents Overview
The guide outlines power-off and power-on test methods for critical system components, covering:
Signal Communication Tests
System signal verification between indoor and outdoor units.
3-wire remote controller signal test (Y1, Y2, Y3 terminals).
DC serial communication expected voltage values for both indoor and outdoor circuits
Fujitsu Component Testing (3)
.
Power Conversion & Drive Components
Diode Bridge (1-Phase / 3-Phase): Converts AC supply to DC voltage.
Expected readings: 0.4 V forward voltage drop per diode; 0.7–0.9 V between + and –
Fujitsu Component Testing (3)
.
Active Filter Module (ACTPM): Improves power factor and supplies DC bus to inverter.
Resistance test range: 360 kΩ – 900 kΩ between terminals
Fujitsu Component Testing (3)
.
Intelligent Power Module (IPM): Drives compressor windings (U, V, W).
Expected diode readings: 0.4 V ± 0.1 V per phase
Fujitsu Component Testing (3)
.
Fan Motor Testing
DC Brushless Motors: Operate at 330–380 V DC (main power) and 15 V DC (control).
Verify diode readings: 0.5 – 1.8 V (white-to-black), 0.8 – 1.1 V (black-to-red)
Fujitsu Component Testing (3)
.
AC Fan Motors: Check resistance across phases; refer to fan-specific tables (typically 5–20 Ω range).
Sensor Testing
Thermistors:
Power-on: Expect 5 V DC supply with a lower return voltage (temperature-dependent).
Power-off: Cross-check resistance values using thermistor tables or the Mobile Technician App
Fujitsu Component Testing (3)
.
Pressure Transducer:
5 V DC supply between red and black; return voltage 0.5–4.5 V proportional to system pressure
Fujitsu Component Testing (3)
.
Electronic Expansion Valve (EEV) Coils
5-Wire / 6-Wire Coils:
Resistance range: 45 – 50 Ω between control wires.
“J Series” high-resistance coils: ~150 Ω per winding
Fujitsu Component Testing (3)
.Always test coil to earth (O/L expected).
Thermistor Reference Table
Standard resistance at 20 °C:
Room Temp = 12.5 kΩ, HEX = 62.9 kΩ, Compressor = 62.5 kΩ.
Voltage typically 2.1–2.3 V DC at 20 °C
Fujitsu Component Testing (3)
.
Test Run Procedure
Manual test run can be activated from the outdoor LED display board if wall controller access is unavailable.
Always terminate test run at the display after completion to return control to the wall controller
Fujitsu Component Testing (3)
.
Technician Notes
Always isolate power before performing resistance or diode tests.
Verify readings against ambient temperature (especially thermistors and motors).
Cross-check anomalies using the Mobile Technician App for updated specifications.
Faulty readings may indicate shorted diodes, open circuits, or PCB failure.