System Signal Test

Indoor and outdoor unit communication diagnostic procedure

Overview

The System Signal Test verifies serial communication between the indoor and outdoor units in a split or multi-system configuration. It confirms whether both units are correctly exchanging control signals through the communication line.

Testing can be completed from either the indoor or outdoor terminal block, allowing technicians to isolate faults involving interconnecting wiring or the indoor and outdoor control boards.

Safety warning - live DC and AC circuits

Testing is performed with power ON. Use insulated probes, wear appropriate personal protective equipment, and do not allow the probes to short adjacent terminals.

Testing conditions

  • Confirm the power supply is active and both units are energised.
  • Use a digital multimeter set to DC voltage.
  • Identify the terminals on both the indoor and outdoor terminal blocks:
TerminalFunction
1L - Live
2N - Neutral
3Signal / serial communication

Test procedure

1. Indoor unit test

  1. Locate the indoor unit terminal block.
  2. Disconnect Terminal 3, the signal wire leading to the outdoor unit.
  3. Measure DC voltage between Terminal 2 (Neutral) and the disconnected signal wire.
  4. This reading represents the outdoor unit signal returning to the indoor connection.
Indoor test reference: Match the indoor model family to the expected DC voltage below.
Indoor model typeExpected signal
AST and ART/C60-120 V DC
ASTA and ASTB40-90 V DC
ASTGApproximately 200 V DC - static
ARTG and three-phase systemsApproximately 295 V DC - static
ARTH50-250 V DC

2. Outdoor unit test

  1. Locate the outdoor unit terminal block.
  2. Disconnect Terminal 3, the signal cable connected to the indoor unit.
  3. Measure DC voltage between Terminal 2 (Neutral) and the disconnected signal wire.
  4. This reading represents the indoor unit signal reaching the outdoor connection.
Outdoor model typeExpected signal
AOTA60-120 V DC
AOTG3-110 V DC
AOTH3-110 V DC

3. Cross-check the communication path

  • A normal signal at one unit but no corresponding signal at the other end indicates a possible damaged, disconnected, or open-circuit interconnecting signal cable.
  • No signal from either unit indicates a possible indoor or outdoor control PCB fault.

Diagnosis and interpretation

ObservationLikely diagnosisRecommended action
Signal voltage is within range at both unitsCommunication is operating normallyNo communication fault detected
Signal is present at one end onlyBroken, loose, or disconnected interconnecting cableInspect, test, and repair the wiring
No signal from either unitPossible indoor or outdoor control PCB faultConfirm the failed board before replacement
Signal is unstable or fluctuates abnormallyPoor termination, damaged wiring, or electrical noiseCheck terminations, cable condition, routing, and earthing

Technical notes

  • Terminal 3 carries a DC serial data signal used for control communication between the indoor and outdoor units.
  • The multimeter displays an average of the pulsed DC signal, so the reading may fluctuate during operation.
  • Always use Terminal 2 (Neutral) as the reference point for these measurements.
  • For multi-split systems, test each indoor-to-outdoor communication path individually.

Reference diagrams

System signal test reference diagram 1
System signal test reference diagram 2
System signal test reference diagram 3
System signal test reference diagram 4